PW9355 Online UPS 30kVA/27kW 220V Input/Output 11 Minutes Full Load - KB3013200000010
- Provides 27kW, 30000VA power / Surge Suppression is Standard
- 11 minute(s) Battery Runtime at Full Load / Attributes include Double conversion online
This is a Powerware PW9355 30kVA/27kW UPS with internal battery and true Double-conversion Online topology.
PW9355 Online UPS 30kVA/27kW 220V Input/Output 11 Minutes Full Load - KB3013200000010
|
General
|
|
|
Attributes
|
Double conversion online
|
|
Form Factor
|
External
|
|
Power
|
|
|
Battery Run Time (max)
|
11 minute(s)
|
|
Power Provided
|
27 kW
|
|
Power Provided
|
30000 VA
|
|
Surge Suppression
|
Standard
|
|
Actual Weight
|
1160.00 lb(s)
|
|
Compatibility Notes
|
General
Diagnostics: full system self-test at startup UPS bypass: automatic on overload or UPS failure Parallel for Redundancy and Capacity: yes, using Powerware Hot Sync technology Overload: (normal operation) 150% for 5 seconds / 125% for 1 minute (online), 110% for 10 minutes
Communications
LCD Display: graphical LCD with blue backlight LEDs: (4) LEDs for notice and alarm Audible alarms: yes Communication ports: (1) RS-232, (1) relay contact, (1) REPO, (2) environmental input Communication slots (2): X-Slot communication bays Power management software: bundled software suite CD
|
|
Contents
|
UPS, documentation
|
|
Physical Dimensions
|
66"h x 20"w x 34.1"d
|
|
Power Notes
|
Power
Rating: 30kVA / 27kW, 0.9 power factor Topology: true double-conversion online UPS
Electrical Input
Nominal input voltage: 208 / 120V, 220 / 127V +15, -20%; 480V / 277V, 600V (480+600 with transformer) Operating frequency: 50 / 60Hz (45 to 65Hz) Input power factor: 0.99 typical Input current distortion: <5% THD
Electrical Output
Nominal output voltage: 208 / 120, 220 / 120VAC; 480 / 227VAC with output transformer Output voltage regulation: ±1% Static; ±4% dynamic with 100% step load recovery within 1 ms response time Efficiency: 91 typical
Battery
Battery type: 9Ah, sealed, lead-acid, maintenance-free Battery replacement: field-replaceable Charger default is 3.4A per battery string. Charger current is configurable from 0.5A to 25A per string with an overall maximum of 34A (limited by input current) Start-On-Battery: allows start of UPS without utility input Battery runtime, full load: 11 minutes (27kW)
|
|