Maintenance Bypass Cabinet, Wall Mountable - NMBHW41
This wall-mountable Maintenance Bypass Cabinet is intended for use with the Nfinity, UPStation
GXT 6 and 10 kVA, or any other UPS with equivalent specifications. Typical applications include supporting
workstations, servers, network, telecom or other sensitive electronic equipment.
The Maintenance Bypass Cabinet was designed to provide maximum system availability to business
critical equipment. The Maintenance Bypass Cabinet allows for transfer of connected loads to an
alternate power path allowing full isolation of the UPS. The UPS can then be turned off and
removed from service with no interruption of power to connected loads.
Maintenance Bypass Cabinet, Wall Mountable - NMBHW41
|
Actual Weight
|
45.00 lb(s)
|
|
Contents
|
Unit, documentation
|
|
Physical Dimensions
|
18"h x 20"w x 8"d
|
|
Power Notes
|
Unit Rating: 16kVA, 100A maximum
Input Data
Nominal input voltage: 208 or 240VAC Input frequency, nominal: 50 or 60Hz Input frequency range: 45-55Hz or 55-65Hz
Output Data (208 / 240, 240, 208)
Output voltage, VAC: 120 / 120 / 208 / 240, 120 / 120 / 240, 120 / 120 / 208 Transfer time: <4 msec typical Output frequency: 50 or 60Hz (same as input)
TB6 Contacts
Maximum voltage: 120VAC Maximum current: 5A
|
|
Returns Policy
|
This product is subject to our return policy. Please see our complete return policy for details.
|
|
Warranty - Labor
|
2 Years
|
|
Warranty - Parts
|
2 Years
|