HP Modular Cooling System - AF098A
HP Modular Cooling System or MCS is designed for high density server and blade deployments. It re-circulates and cools the hot server exhaust air through heat exchangers residing in the MCS unit. The air is then expelled in front of the enclosed rack at a much lower temperature providing sufficient cool air for a load of 30KW of servers or blades. The MCS ships attached to a specially adapted 42U 10000 Series G2 rack 600mm wide (10642).
The MCS unit contains three fans and three heat exchangers deployed along the full height of the rack to ensure that all the equipment installed receives sufficient cooled air. All fans and heat exchangers are swappable while the unit is online, providing great servicing flexibility. Redundant power is ensured through a failover power switch that can be connected to two power sources. The environmental monitor controls the air temperature to the servers and adjusts automatically to meet the pre-established air temperature goal. The environmental monitor interacts with HP SIM (Systems Insight Manager) via SNMP traps.
The Water Hookup kit is made available as a separate kit to prepare the water hookup ahead of the arrival of the MCS.
HP Modular Cooling System - AF098A
|
General
|
|
|
Product Type
|
Cooling kit
|
|
Product Type
|
Rack
|
|
Actual Weight
|
1130.00 lb(s)
|
|
Compatibility Notes
|
Features: 30KW of cooling capacity for high density deployment of servers and blades. 42U rack height and 1.5 racks wide to maintain datacenter tiling configuration Ships pre-attached to HP 10642 G2 Series Rack, Environmental Monitor and control with SNMP integration to Systems Insight Manager (SIM) Hot swappable heat exchangers and fans. Power Input Redundancy for dual power source. Condensate Evacuation system to prevent condensation from entering air stream. 2750 CFM of chilled air placed in front of the servers and / or blades
|
|
Contents
|
Modular cooling system, documentation
|
|
Physical Dimensions
|
78.7"h x 35.8"w x 50"d
|
|
Ports/Connectors
|
Control panel Multi-function LCD status and control console SIM 5.0 Integration Yes, via SNMP traps (1) RJ 45 Plug
|
|
Power Notes
|
Power supply: Nominal Input Voltage: 208-240 VAC + - 10% Frequency range (min-max): 50 / 60 Hz Input Power: 2000 Watts Max Single phase: Yes Rated line current: 15A per line cord Max inrush current: 54A peak for 20 ms per line cord Dropout carry through time at min voltage: 20 ms Circuit breaker rating: 20A per line cord Power factor correction: >0.98 at all loads Ground leakage current (mA): <3.0 (mA) per line cord Input Connections: NEMA L6-20P Power Cords: 2 (for redundancy) Power input redundancy: Yes, with auto failover switch
Cooling: Cooling agent: Primary or auxiliary chilled water supply Condensate evacuation tube: Yes Air temperature regulation: Yes Heat exchangers: 3 Fans: 3 Rack Front door: Transparent polycarbonate insert behind mesh Rack Rear doors (split): Solid, no mesh Chilled water connections: Bottom rear MCS mounting location: Left hand side Side panels included: Yes Max Cooling capacity: 30KW Air Temperature to servers: Settable, suggested at 68-77 °F ( 20-25°C) Air Flow to servers: 2750 CFM Max Recommended Chilled Water inlet temperature: 45.0 °F ( 7.00 °C) Maximum Chilled Water Flow Rate: 20 gpm (1.27 lps) Chilled Water Pressure Drop: 25 psid Water connections: 1.25 in (31.8mm) Coupling type: 1.25 in (31.8mm) Quick-disconnect coupling, Parallel (parallel-to-tapered adapter included in AF079A) Flexible hose length (pre-installed): 36 in (914mm) Pipe thread: Parallel (parallel-to-tapered adapter included)
|
|