Galaxy 4000 40kVA/32kW 208V 3-Phase Online UPS, Extended Runtime - GLF40KF
- Provides 208V, 32000watt(s), 40000VA power / Surge Suppression is Standard
- Connector(s): Hardwired
- Attributes include Double conversion online, Automatic voltage regulation (AVR)
The MGE Galaxy UPS gives you technology that increases performance and reliability. Its Double-conversion Online technology fully isolates and protects against all power quality disturbances. The upstream harmonics management allows a generator friendly installation. The MGE Galaxy offers features such as paralleling capability for both capacity and redundancy, full front access for ease of serviceability, user friendly graphical display with multiple language options, and SNMP with network based power management options.
The Galaxy 4000’s IGBT rectifier significantly minimizes input harmonics and the Power Factor Corrected Input reduces installation costs due to smaller cabling and generator costs. Unmatched from a performance standpoint, the Galaxy 4000’s unique fault tolerant architecture safely manages output faults without compromising the UPS, while the Digital Power Quality Management System provides precision voltage regulation on a consistent basis.
Galaxy 4000 40kVA/32kW 208V 3-Phase Online UPS, Extended Runtime - GLF40KF
|
Connectivity
|
|
|
Communication Interface
|
Ethernet
|
|
Connector
|
Hardwired
|
|
General
|
|
|
Attributes
|
Automatic voltage regulation (AVR)
|
|
Attributes
|
Double conversion online
|
|
Power
|
|
|
Surge Suppression
|
Standard
|
|
Power Provided
|
208 V
|
|
Power Provided
|
40000 VA
|
|
Power Provided
|
32000 watt(s)
|
|
Actual Weight
|
2565.00 lb(s)
|
|
Compatibility Notes
|
Communications & Management
Available SmartSlot Interface Quantity: (2) Control panel: Multi-function LCD status and control console Emergency Power Off (EPO): Yes
Features
Audible alarms Automatic internal bypass Front-access servicing Generator compatible LCD graphics display Manual maintenance bypass Network manageable
|
|
Contents
|
UPS, Web / SNMP card, documentation
|
|
Physical Dimensions
|
72.1"h x 33.5"w x 35.6"d
|
|
Ports/Connectors
|
Output Connections: (1) Screw Terminals Input Connections: Hard Wire 5-wire (3PH + N + G)
|
|
Power Notes
|
Output
Output Power Capacity: 32kW/40kVA Maximum Configurable Power: 32kW/40kVA Nominal Output Voltage: 208VAC 3-PH Efficiency at Full Load: 93.5% Output Voltage Distortion: Less than 3% Output Frequency (sync to mains): 60Hz Waveform Type: Sine wave Output Voltage Tolerance: + / -1% static and + / - 5% at 100% load step Efficiency at Half Load: 92%
Input
Bypass: Built-in Static Bypass Nominal Input Voltage: 208VAC 3-PH Input Frequency: 60Hz + / - 3Hz Input voltage range for main operations: 166-239V Input Total Harmonic Distortion: Less than 3% for full load Type of Input Protection Required: 3-pole breaker
Batteries
Battery Type: VRLA Nominal Battery Voltage: 240V Efficiency in Battery Operation: 95%
|
|